How to maintain the high efficiency filter in the weighing room

1. Maintenance category The maintenance category is divided into three categories: daily, primary and secondary maintenance.

2, maintenance interval maintenance categories: daily maintenance, primary maintenance, secondary maintenance.

Maintenance interval: 15 minutes before and after the shift; three months and one year.

3, maintenance content 3.1 daily maintenance (1) before cleaning the machine, you must first turn off the power to ensure the safety of the human machine.

(2) Wipe the work surface and outer surface of the machine with a clean cloth.

(3) After each work, clean the cabinet, siding and floor. After work, the operator will wipe the surface of the equipment once and visually inspect the surface of the equipment clean and clean.

(4) Adjusting the exhaust air volume: 10% of the air volume in the weighing room needs to be discharged to the outside, and the air volume can be adjusted through the knob on the panel.

(4) The daily insurance is generally 15 minutes.

3.2 Level 1 Maintenance (1) Includes daily maintenance content.

(2) Replacement of the filter.

(a) High-efficiency filter replacement The initial pressure difference is recorded after installation. When the final resistance reaches 1.5 times the initial resistance (about 380 Pa), the primary and intermediate-effect filters need to be cleaned or replaced.

(b) When the high-efficiency differential pressure gauge exceeds the initial differential pressure by 1.5 times (at this time, due to high-efficiency clogging, the differential pressure reaches the life value), please replace the high-efficiency filter, and pay attention to the following when replacing:

(I) When replacing the high-efficiency filter, special attention should be paid to protecting the filter paper intact during unpacking, handling and installation. It is forbidden to touch the filter paper by hand to cause damage.

(II) Gently push and pull gently to remove the confluent film, carefully place the confluent film, do not break, you can see the high efficiency filter.

(III) Two people cooperate to remove the high efficiency filter.

(IV) Place the new high-efficiency filter (high-efficiency filter air inlet with sealing strip) in the original high-efficiency position (the distance between the four sides of the filter and the screw is uniform), press the clamp and smoothly lock the nut.

(V) When tightening the clamp, the force should be uniform and appropriate. It is necessary to ensure that the high-efficiency filter is stable and reliable, and that the high-efficiency filter is prevented from leaking due to deformation. After replacement, the cleanliness of the equipment should be checked with a dust particle counter. Framed leaks can be blocked with a neutral sealant.

(c) Check the looseness of the fastening bolts of the fan and press it if necessary.

(d) Regularly (usually 3 months) use a dust detector (dust particle counter) to measure the cleanliness of the room. When the technical requirements are not met, the high efficiency air filter must be replaced. When the high-efficiency filter breaks or leaks, it needs to be replaced immediately. Due to the cleanliness of the use environment and the frequency of use, the replacement cycle of the high-efficiency filter is also different. Generally, it is preferable to use the high-efficiency filter differential pressure value to reach 1.5 times of the initial resistance.

3.3 secondary maintenance (1) includes all the contents of the first level maintenance.

(2) Open the maintenance panel and carry out maintenance and repair on the fan and electric control box. When replacing the fan, please pay attention to the position of the wiring, so as to avoid the normal operation of the device due to wiring errors after replacement.

(3) The fan does not require special maintenance, and an operation check is performed once a year and the screw at the wire joint is loosened.

(4) The replacement and maintenance of electrical equipment must be completed by electrical engineering and technical personnel. Before the replacement, the wiring should be marked or photographed. After replacement, the wiring should be carried out according to the original wiring.

(5) Check the differential pressure gauge every year.

Shanghai Sujing Industrial Co., Ltd. If you have any needs, you can pass it with us at any time. Thank you very much for your support to Sujing and look forward to cooperating with you.

have a pleasant workday!

Thankyou&Bestregard!

SUJING—JINGHUA

Whole Head Black Garlic

Whole Bulb Black Garlic is made from Whole Bulb Fresh Garlic.Generally,Whole Black Garlic has 6-8 or 8-12 small cloves.Putting fresh garlic into the Black Garlic Machine for 18-20days,we can get whole bulb black garlic.Black garlic has sweet taste and soft texture.Compared with fresh garlic,it is becoming more and more popular.

Whole Black Garlic

Whole Bulb Black Garlic,Black Garlic Food,Multi Bulb Black Garlic,Fermentated Black Garlic Granule

Zhucheng Tongxi Commercial And Trade Co.,Ltd. , https://www.blackgarlicgroup.com